Sign In | Join Free | My xuijs.com |
|
Brand Name : GDZX
Model Number : ZXHQ-C
Certification : ISO9001
Place of Origin : China
MOQ : 1Set
Price : US $1989.00-$4236.00 /SET
Payment Terms : L/C, T/T, Western Union, MoneyGram, D/A, D/P, WeChat, Paypal
Supply Ability : 1200sets/year
Delivery Time : 7-20 work days
Packaging Details : Packing wooden case or carton
Product name : Transformer Calibrator
Use environment : Temperature:5 ℃ -- 40 ℃,Relative humidity: < 80% (25 ℃) ,altitude: < 2500m
Impedance (Ω) : 0.0001 ~ 20.0 resolution: 0.0001
Dial indicator : level 1.5 (optional level 1)
Harmonic suppression ratio : > 40dB
Boundary dimension : 260 × 350 × 150 mm
Weight : 6kg
Power consumption : < 15va (without micro printer);< 25VA (with micro printer)
Multifunctional AC 220V Electronic Transformer Field Calibrator With DSP Technology
Product introduction
ZXHQ-C transformer calibrator is a new kind of automatic testing instrument. It uses electronic technology to directly decompose the error signal of the transformer, and after proper calculation, the percentage point, in-phase error and orthogonal error of the transformer are displayed in digital quantity at the same time. The instrument has the advantages of simple operation, direct reading, rapid measurement, low power consumption and labor intensity, small volume, light weight, easy carrying and field test, and can be tested under 5% rated working current (voltage).
Features
Use environment | |
1. Temperature: 5 ºC -- 40 ºC relative humidity: < 80% (25 ºC) altitude: < 2500m; | |
Power frequency: 50Hz ± 0.5Hz power voltage: 220V ± 5V | |
2. Measurement range: | In phase component (%): 0.0001 -200.0 resolution: 0.0001 Orthogonal component (min): 0.001-700.0 resolution: 0.001 Impedance (Ω): 0.0001 -20.0 resolution: 0.0001 Mobility (MS): 0.0001- 20.0 resolution: 0.0001 |
3. Basic error: | In phase component: Δ x = ± (x × 2% + y × 2%) ± DX (with level 1 option); Orthogonal component: Δ y = ± (x × 2% + y × 2% × 34.48) (Level 1 optional); "X", "Y" - display value of the instrument; "DX, Dy" - quantization error of instrument Dx = 2, Dy = 5 |
4.Dial indicator: level 1.5 (optional level 1) | Scope of work: (1). Current: (1% - 149%) in (in = 5a) (5%-149%)In(In =1A); (2) Voltage: (5% - 149%) UN (UN = 100V, 150V, 100V/ √ 3) (5%-149%)Un(Un =100V/3); |
Workload: (1) Current: TO to TX<0.12Ω cos Φ = 1; (2) Voltage: A to X<0.25va (100V); | |
5. Power consumption: | <15va (without micro printer); <25VA (with micro printer); |
6.Harmonic suppression ratio: | >40dB |
7. Boundary dimension: | 260 × 350 × 150 mm |
8. Weight: | 6kg |
![]() |
Multifunctional AC220V Electronic Transformer Field Calibrator With DSP Technology Images |